G-0400 REFRIGERANT FIELD
CONVERSION PROCEDURE
R-502 to R-402B
FOR MODELS
WARNING!
GR-0400A GR-0401W GR-0490N
GD-0402A GD-0403W GD-0492N
GY-0404A GD-0405W GY-0494N
Use only R-402B as
retrofit refrigerant. Other
replacement refrigerants
may cause poor performance
and/or component failure.
EQUIPMENT MODIFICATION REQUIREMENTS
Component
Change Required
Compressor
None (replacement compressor is precharged with POE oil)
Expansion Valve (TXV)
High Pressure Cut-out
Low Pressure Cut-out (Remotes)
Fan Cycling Control (Air-cooled)
All Solenoid Valves
Water Regulating Valve (Water-cooled)
Heat Exchanger
None
None
None
None
None
None
None
None
None
None
None
None
Electrical Wiring
Branch Circuit Fuse Size
Air-cooled Condenser
Water-cooled Condenser
Evaporator
SYSTEM PERFORMANCE AFTER CONVERSION
Daily Ice Production
G-0400 8% increase
Energy Efficiency
5% increase
Operating discharge (high) pressure: air-cooled models will run 20-30 psig (138-207 kPa gauge)
higher than R-502 pressures published in service manuals. Set water-cooled head pressure the same
as R-502 settings.
Operating suction (low) pressure: will run 1-3 psig (7-21 kPa gauge) higher than R-502 pressure
published in service manuals.
8010513
Sheet 1 of 2
08/96
Manitowoc Equipment Works
Division of The Manitowoc Company, Inc. • 2110 South 26 Street, P.O. Box 1720, Manitowoc , WI 54221-1720 USA
Telephone 414-682-0161 • Fax - Sales: 414-683-7589 • Service/Parts: 414-683-7585 • Other: 414-683-7879
|
Kyocera Photo Scanner FS 2020D User Manual
Lindy Projector 32498 User Manual
Linear Utility Trailer 2500 2346 LP User Manual
Mach Speed Technologies MP3 Player T2810C User Manual
Magnadyne Automobile Alarm X4 User Manual
Magnat Audio TV Cables Neo Flex 130 User Manual
Magnavox Portable CD Player AZ 8700 User Manual
Makita Power Screwdriver BFS440 User Manual
Marantz Stereo Receiver SR8200 User Manual
Micro Innovations Mouse PD895P User Manual