AK-11
Digital Keyless Entry System
Installation and Programming Instructions
(760) 438-7000
USA & Canada (800) 421-1587 & (800) 392-0123
Toll Free FAX (800) 468-1340
COMPONENT LOCATIONS
RED/GREEN
POWER/ACCESS
INDICATOR
YELLOW
"LOCKOUT"
INDICATOR
JUMPER JP2
RESETS
MASTER CODE
TERMINAL
BLOCK J3
OUTPUTS
NIGHT
LIGHT
JUMPER JP1
REMOVE TO
REDUCE
TACTILE
KEYPAD
TERMINAL BLOCK J4
POWER AND INPUTS
BEEPER SOUND
KEYLOCK
Figure 1. Component Locations
WIRING DIAGRAM
TYPICAL GATE INSTALLATION WIRING
TYPICAL DOOR INSTALLATION WIRING
AK-11
AK-11
J3
J3
N.O.
COMMON
N.C.
N.O.
COMMON
N.C.
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
RELAY #1
RELAY #1
TO ALARM
SYSTEM
J4
J4
OUTPUT #3
OUTPUT #4
N.O.
OUTPUT #3
OUTPUT #4
N.O.
1
2
3
4
5
6
1
2
3
4
5
6
POWER
POWER
INHIBIT
DOOR SENSE
COMMON
RELAY #2
COMMON
N.C.
RELAY #2
COMMON
N.C.
COMMON
REQUEST-TO-ENTER
EARTH GROUND
REQUEST-TO-ENTER
EARTH GROUND
COMMON
GROUND
COMMON
GROUND
OPEN
INHIBIT
TIMER
FIRE
ACCESS
ELECTRIC
DOOR
ALARM CONTACT
STRIKE
REQUIRED WIRING
OPTIONAL WIRING
AUXILIARY
POWER
OPEN
TO ALARM
SYSTEM
POWER
SUPPLY
DOOR SWITCH
GATE OPERATOR
Figure 2. Wiring Diagram
3
INSTALLATION
To avoid damage to the unit from static discharges, connect the
EARTH GROUND terminal to a good earth grounding point.
Suggested wiring size is 18 AWG for earth ground and power (up
to 500 feet of 18 AWG wire can be run for power, use larger wire
for longer runs). Use 22 AWG or larger (depending on the load)
for all other connections.
PEDESTAL
! CAUTION: If the unit is AC powered, and one side of the
power transformer secondary is connected to earth
ground, connect the grounded side to the “-” power
terminal of the unit.
Select a location for the keypad. For door access control
installations, mount the keypad near the controlled door. For gate
control installations, mount the keypad in clear view of the gate,
but far enough from the gate so the user cannot touch the gate
from the keypad.
# WARNING: TO AVOID SERIOUS INJURY OR DEATH, MAKE
SURE THAT THE UNIT IS FAR ENOUGH FROM THE GATE
SO THAT THE USER CANNOT TOUCH THE GATE WHILE
OPERATING THE KEYPAD. HOWEVER, THE GATE MUST
BE FULLY VISIBLE FROM THE KEYPAD.
MOUNT BACKPLATE WITH
SECURITY BOLTS AND LOCKNUTS
Figure 3. Pedestal Mounting Keypad Backplate
Pedestal Mounting
The AK-11 keypad can be mounted on a standard pedestal.
Use four security bolts and locking nuts to secure the
keypad’s backplate to the pedestal (see Figure 3).
WALL MOUNTING
Wall Mounting
The AK-11 keypad can be mounted directly to a wall or flat
surface.
Use the appropriate fasteners to secure the keypad’s
backplate to the mounting surface.
When mounting the keypad to a concrete wall, use
concrete wedge anchors or molly anchors (see Figure 4).
USE CONCRETE
WEDGE ANCHORS
OR MOLLY ANCHORS
Figure 4. Wall Mounting Keypad Backplate
4
Gate Control
Door Control
Route four wires between the gate and the keypad (two for
power, two for control).
Install a low voltage electric door strike for unlocking the
door.
Connect the gate operator’s auxiliary or radio power output
terminals to the keypads POWER input terminals (observe
wiring polarity).
Connect the gate operator’s OPEN terminals to the
keypad’s Relay #1 COMMON & N.O. terminals.
ꢁNOTE: For operator wiring specifics, refer to the gate
operator’s wiring diagram.
Choose a location for the power supply or transformer.
Route two wires between the power supply and the
keypad. Connect the power supply’s output terminals to
the keypad’s POWER input terminals (observe wiring
polarity).
Route two wires between the door strike and the keypad.
Connect one of the door strike wires to the keypad’s Relay
#1 N.O. terminal. Connect the other door strike wire to the
If a request-to-enter pushbutton or fire access keyswitch
is going to be used, route two wires from the keypad to the
normally open switch. Connect the wires to the normally
open switch and to the keypad’s REQUEST-TO-ENTER
and COMMON terminals.
If an inhibit switch or timer is going to be used, route two
wires from the keypad to the inhibit switch or timer relay.
Connect the inhibit switch/timer terminals to the keypad’s
INHIBIT and COMMON terminals.
keypad’s POWER terminal. Connect a wire between the
keypad’s POWER - terminal and the Relay #1 COMMON
+
terminal.
If a request-to-enter pushbutton or fire access keyswitch
is going to be used, route two wires from the keypad to the
normally open switch. Connect the wires to the normally
open switch and to the keypad’s REQUEST-TO-ENTER
and COMMON terminals.
To use the door sense feature to detect forced entry or
door ajar conditions, install a normally closed door switch
on the door and route two wires from the switch to the
keypad. Connect the door switch to the keypad’s DOOR
SENSE and COMMON terminals.
ꢁNOTE: If the INHIBIT input is going to be used, it must be
programmed to select that input type. See the Programming
Options section of this manual.
If an inhibit switch or timer is going to be used, route two
wires from the switch or timer to the keypad. Connect the
inhibit switch/timer terminals to the keypad’s INHIBIT and
COMMON terminals.
ꢁNOTE: Either door sense or inhibit can be used. Both features
cannot be used at the same time.
DOOR
SENSE
SWITCH
AK-11
KEYPAD
GATE
OPERATOR
(BEHIND GATE)
2 WIRES
FOR DOOR
SENSE
2 WIRES FOR
REQUEST-TO-ENTER
FIRE
ACCESS
KEYSWITCH
AK-11
KEYPAD
2 WIRES
FOR
POWER
2 WIRES FROM AK-11
TO TRIGGER GATE OPEN
2 WIRES FROM OPERATOR
FOR AK-11 POWER
FROM
POWER
SUPPLY
ELECTRIC
DOOR
STRIKE
2 WIRES
FOR DOOR
STRIKE
Figure 5. Gate Installation
Figure 6. Door Installation
5
Setting Entry Code Length
Default: 4 digits
FACTORY DEFAULTS
MASTER PROGRAMMING CODE. . . . . . . . . . . . . . . . . . . . 123456
ENTRY CODE LENGTH . . . . . . . . . . . . . . . . . . . . . . . . . . 4 DIGITS
REQUEST-TO-ENTER OUTPUT . . . . . . . . . . . . . . . . . . RELAY #1
ALARM SHUNT OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . DISABLED
FORCED ENTRY OUTPUT . . . . . . . . . . . . . . . . . . . . . OUTPUT #3
DOOR AJAR OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . OUTPUT #4
RELAY #1 ON TIME . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SECONDS
RELAY #2 ON TIME . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SECONDS
SOLID STATE OUTPUT #3 ON TIME . . . . . . . . . . . . 2 SECONDS
SOLID STATE OUTPUT #4 ON TIME . . . . . . . . . . . . 2 SECONDS
DOOR SENSE/INHIBIT INPUT. . . . . . . . . . . . . . . . DOOR SENSE
KEYPAD LOCKOUT OUTPUT . . . . . . . . . . . . . . . . . . . . DISABLED
KEYPAD ACTIVE OUTPUT . . . . . . . . . . . . . . . . . . . . . . DISABLED
DOWNLIGHT ON-TIME. . . . . . . . . . . . . . . . . . . . . . . . . 2 MINUTES
BEEPER SOUNDS WHEN KEY PRESSED . . . . . . . . . . . . . . YES
BEEPER SOUNDS DURING RELAY #1 . . . . . . . . . . . . . . . . . . NO
BEEPER SOUNDS DURING RELAY #2 . . . . . . . . . . . . . . . . . . NO
BEEPER SOUNDS DURING OUTPUT #3. . . . . . . . . . . . . . . . . NO
BEEPER SOUNDS DURING OUTPUT #4. . . . . . . . . . . . . . . . . NO
KEYPAD LOCKOUT COUNT . . . . . 3 TRIES BEFORE LOCKOUT
ANTI-PASSBACK TIME . . . . . . . . . . . . . . . . NO ANTI-PASSBACK
Press: 0 3 Length
#
#
Length = 1 - 6 for entry code length
ꢁNOTE: If the Entry Code Length is going to be changed from
the factory default of four digits, make this change first, before
programming any entry codes.
Adding a New Entry Code
Press: 0 1 Code Code Action
#
#
#
#
Code = The new entry code: 1-999999, depending on code length
Action = Relay output entry code will activate as follows:
1 = Relay #1, timed open
2 = Relay #2, timed open
3 = Both Relays, timed open
10 = Relay #1, toggled
20 = Relay #2, toggled
30 = Both Relays, toggled
12 = Relay #1 toggled; Relay #2, timed open
21 = Relay #1, timed open; Relay #2 toggled
The yellow LED will flash quickly while the AK-11 searches its
memory for available space and duplicate entries. The green
LED will light when the new code is stored.
BASIC PROGRAMMING
If the new entry code chosen is already being used for another
entry code, the red LED will light. A new unique code needs to
be entered.
When the AK-11 is in programming mode, both LEDs will turn off
until programming begins. After a programming option number
is entered the yellow LED will blink. This indicates that the AK-11
is ready to accept the new programming data. After the new data
entry is complete, the green LED will light while the data is being
stored. The red LED will light if any programming data is entered
incorrectly, and the command will have to be fully re-entered.
ꢁNOTE: Leading zeros (zeros before the code number, i.e.
0001) do not need to be entered when programming a new
entry code. The AK-11 will internally add any zeros to fill all
digits determined by the entry code length setting. Leading
zeros will have to be entered by the user when entering their
code to gain access.
Entering Programming Mode
Erasing a Single Entry Code
The 6-digit Master Programming Code (default = 123456) is used
to enter Programming Mode.
Press: 0 2 Code Code
#
#
#
Code = The entry code to delete.
Press:
Master Code = the current 6-digit Master Programming Code
9
Master Code
# #
The yellow LED will flash quickly while the AK-11 searches its
memory for the code to erase. The green LED will light when the
code is erased.
Exiting Programming Mode
Erasing All Entry Codes
# WARNING: Performing this command will remove all entry
codes from the memory.
Press: * * #
The red LED will light when Programming Mode is exited.
ꢁNOTE: The AK-11 will automatically exit Programming Mode
after two minutes of inactivity.
Press: 9 7 0 0 0 0 0 0 0 0 0 0 0 0
#
#
erased. This may take up to 15 seconds.
#
ꢁNOTE: The green LED will light while the memory is being
Re-entering a Command After a Mistake
If the red LED lights, indicating an incorrect entry, or a wrong key
is pressed during programming, to clear the keypad and re-enter
the command:
Changing the 6-Digit Master Programming Code
Press: 9 8 Master Code Master Code
#
#
#
Press:
9
#
Master Code = The new 6-digit Master Programming Code
*
New master code: _____________________
6
Select Alarm Shunt Output
Default: No Output
PROGRAMMING OPTIONS
Sets which output activates during the time access is granted. (Use
this output to shunt alarm contacts attached to the access door.) This
output may be timed or latched.
Select Door Sense or Inhibit Input
Default: Door Sense
The input on terminal block J4, terminal #3 can be programmed
for DOOR SENSE or INHIBIT.
Press: 1 5 Output
#
#
Output = Output to Activate (0-4)
1 = Relay #1 2 = Relay #2 3 = Output #3,
4 = Output #4 0 = No Output
Press: 1 0 Input
#
#
Input = 1 for Inhibit,
= 0 for Door Sense
Select Request-to-Enter Output
Default: Relay #1
Sets which output activates when the Request-to-Enter input is
grounded. This output remains activated for at least the length of time
specified by the On-times for the relays or outputs. If the
Request-to-Enter input continues to be grounded beyond the time
specified by the On-times for the relays or outputs, the output will
remain activated as long as the Request-to-Enter input remains
grounded.
When programmed for DOOR SENSE, if an open condition on
the input occurs before access is granted (with an entry code or
with the request-to-enter input) a FORCED ENTRY output will
occur. If an open condition remains 60 seconds after a relay
activation for access, a DOOR AJAR output will occur.
When programmed for INHIBIT, a closed condition on the input
will prevent relay #1 from activating when access is requested
(with an entry code). This mode is typically used with an external
timer to disable the access device at certain times.
Press: 1 6 Output
#
#
Output = Output to Activate (0-4)
1 = Relay #1 2 = Relay #2 3 = Output #3
4 = Output #4 0 = No Output
Select Forced Entry Output
Default: Output #3
Sets which output activates if the Door Sense input opens before
access is granted. This output is not timed.
Relay #1 On-time
Sets the length of time Relay #1 activates when triggered.
Default: 2 Seconds
Press: 1 1 Output
#
#
Press: 2 1 Seconds
Output = Output to Activate (0-4)
1 = Relay #1 2 = Relay #2 3 = Output #3
4 = Output #4 0 = No Output
#
#
Seconds = Output time in seconds (0-60)
Relay #2 On-time Default: 2 Seconds
Sets the length of time Relay #2 activates when triggered.
Select Door Ajar Output
Default: Output #4
Sets which output activates if the Door Sense input stays open after
access is granted. This output is not timed.
Press: 2 2 Seconds
#
#
Seconds = Output time in seconds (0-60)
Press: 1 2 Output
#
#
Output = Output to Activate (0-4)
1 = Relay #1 2 = Relay #2 3 = Output #3
4 = Output #4 0 = No Output
Solid-state Output #3 On-time Default: 2 Seconds
Sets the length of time Output #3 activates when triggered.
Press: 2 3 Seconds
#
#
Seconds = Output time in seconds (0-60) 99 = Toggle mode
Select Keypad Lockout Output
Default: No Output
Sets which output activates when the keypad is “locked out” after too
many incorrect entry code attempts. The lockout time is 60 seconds.
Solid-state Output #4 On-time
Sets the length of time Output #4 activates when triggered.
Default: 2 Seconds
Press: 1 3 Output
#
#
Output = Output to Activate (0-4)
1 = Relay #1 2 = Relay #2 3 = Output #3
4 = Output #4 0 = No Output
Press: 2 4 Seconds
#
#
Seconds = Output time in seconds (0-60)
99 = Toggle mode
Select Keypad Active Output
Sets which output activates when any keys are pressed. This output
is timed.
Default: No Output
Set Downlight On-Time Default: 2 Minutes
Sets the time duration that the downlight remains on after a key press.
Press: 2 5 # Duration #
Press: 1 4 Output
#
#
0 = Always off 1 = 1 minute 2 = 2 minutes 3 = 3 minutes
4 = 4 minutes 99 = Always on
Output = Output to Activate (0-4)
1 = Relay #1 2 = Relay #2 3 = Output #3
4 = Output #4 0 = No Output
7
Beep Sounds on Keystrokes
Selects whether or not the keypad beeps as each key is pressed.
Default: Yes
Master Reset
! CAUTION: Performing a master reset will clear the entire
memory of the AK-11 and return all programmable options
to the factory default values. ALL ENTRY CODES WILL BE
ERASED.
Press: 4 0 Sound
#
#
Sound = 1 for Yes = 0 for No
STEP 1 Disconnect power from the keypad.
STEP 2 Press and hold down the
STEP 3 Apply power to the keypad, continue holding the keys down
until the red LED starts flashing.
and
keys.
#
Beep Sounds During Relay #1
Default: No
Selects whether or not the keypad beeps during Relay #1 activation.
*
STEP 4 Release the keys. The red and yellow LEDs will remain lit
until the process is complete, then the yellow LED will go out.
Press: 4 1 Sound
#
#
Sound = 1 for Yes = 0 for No
Resetting the Master Code
STEP 1 Open the AK-11 case.
STEP 2 Locate jumper JP2. This jumper is used to reset the master
code.
Beep Sounds During Relay #2
Selects whether or not the keypad beeps during Relay #2 activation.
Default: No
STEP 3 With power applied to the keypad, remove jumper JP2. The
keypad will begin to beep, signaling that the code has been
reset.
Press: 4 2 Sound
#
#
Sound = 1 for Yes = 0 for No
STEP 4 Replace jumper JP2.
THE MASTER PROGRAMMING CODE IS NOW 123456.
Beep Sounds During Output #3
Selects whether or not the keypad beeps during Output #3 activation.
Default: No
Press: 4 3 Sound
#
#
Sound = 1 for Yes
= 0 for No
Beep Sounds During Output #4
Selects whether or not the keypad beeps during Output #4 activation.
Default: No
Press: 4 4 Sound
#
#
Sound = 1 for Yes
= 0 for No
Keypad Lockout Count
Default: 3 Tries
Sets the number of incorrect entry code attempts allowed before the
keypad “locks out”.
Press: 5 0 Attempts
#
#
Attempts = Number of attempts before lockout (2-7)
Anti-passback Time Default: No Anti-passback
Sets the length of time an entry code will not function after it is used.
Press: 5 1 Minutes
#
#
Minutes = Time in Minutes (1-4)
0 = No Anti-passback
8
Solid State Outputs
Locking Keypad
The two solid state outputs (Output #3 & Output #4) can be
programmed to activate during various conditions. These
outputs can be used to activate indicators or sounders. See
Figure 7 for wiring examples using the solid state outputs.
After the installation is complete. Lock the keypad using the
keylock (see Figure 9).
DC
POWER
SOURCE
ELECTRONIC
BEEPER
1K
2K
Ω @ 12 volts
Ω
@ 24 volts
LED
LED
EACH
OUTPUT
100 mA
MAXIMUM
OUTPUT #3
OUTPUT #4
EXAMPLE 1: OUTPUT #3 LIGHTS AN LED,
OUTPUT #4 LIGHTS AN LED AND SOUNDS A BEEPER
HOOK KEYPAD
ONTO BACKPLATE
EACH
OUTPUT
100 mA
MAXIMUM
OUTPUT #3
OUTPUT #4
LOW VOLTAGE
LAMP
POWER
SOURCE
N.O. ZONE
ALARM PANEL
COMMON
USE KEY TO
LOCK KEYPAD
END-OF-LINE
RESISTOR
COMMON
GROUND
Figure 9. Locking the Keypad Case
EXAMPLE 2: OUTPUT #3 LIGHTS A LAMP POWERED FROM AN EXTERNAL
SOURCE, OUTPUT #4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE
Figure 7. Using the Solid State Outputs
Beeper Sound Level
The keypad’s beeper can be set to low or high level.
If the keypad’s beeper is too loud for the keypad’s location,
remove jumper JP1 (see Figure 8).
REMOVE JUMPER JP1 TO REDUCE
THE SOUND LEVEL OF THE BEEPER
Figure 8. Removing Beeper Jumper
9
AK-11 OPERATION
ꢀ Users of the AK-11 have up to 40 seconds to key in
their entry code.
ꢀ Up to eight seconds are allowed between each
keystroke.
ꢀ All digits of the entry code must be entered. Example:
If the code is 0042, the user must enter “0 0 4 2”.
ꢀ If the wrong key is pressed, pressing the
key will
*
reset the keypad. The correct code can then be
re-entered.
ꢀ After a correct code is entered, the red LED will turn
green and the programmed relay will activate for the
programmed time.
ꢀ If the number of incorrect codes entered exceeds the
keypad lockout count, the yellow LED will light,
indicating that the keypad is locked out. The lockout
will remain for one minute.
ꢀ After a valid code has been entered, it will be
unusable until the anti-passback time expires.
YELLOW LED WILL LIGHT
DURING KEYPAD LOCKOUT IF
TOO MANY INCORRECT CODES
ARE ENTERED
RED LED TURNS
GREEN WHEN
ACCESS IS GRANTED
PRESS STAR KEY TO
RESET KEYPAD IF THE
WRONG KEY IS PRESSED
USERS HAVE UP TO
40 SECONDS TO ENTER
THEIR COMPLETE CODE
Figure 10. Operating AK-11
10
MANAGER’S ENTRY CODE LOG
NAME
ADDRESS OR APARTMENT NUMBER
ENTRY CODE
RELAY NUMBER
◊1 Timed
◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊1 Timed ◊2 Timed
◊1 Toggled ◊ 2 Toggled
◊2 Timed
11
LINEAR LIMITED WARRANTY
FCC NOTICE
This Linear product is warranted against defects in material and
workmanship for twenty-four (24) months. The Warranty
Expiration Date is labeled on the product. This warranty
extends only to wholesale customers who buy direct from
Linear or through Linear’s normal distribution channels. Linear
does not warrant this product to consumers. Consumers
should inquire from their selling dealer as to the nature of the
dealer’s warranty, if any. There are no obligations or liabilities
on the part of Linear LLC for consequential damages
arising out of or in connection with use or performance of
this product or other indirect damages with respect to loss of
property, revenue, or profit, or cost of removal, installation, or
reinstallation. All implied warranties, including implied warranties
for merchantability and implied warranties for fitness, are valid only
until Warranty Expiration Date as labeled on the product. This
Linear LLC Warranty is in lieu of all other warranties express
or implied.
Changes or modifications not expressly described in this manual
or approved by the manufacturer could void the user’s authority
to operate the equipment.
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful
interference to radio communications. However, there is no
guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
° Reorient or relocate the receiving antenna.
All products returned for warranty service require a Return
Product Authorization Number (RPA#). Contact Linear Technical
Services at 1-800-421-1587 for an RPA# and other important
details.
° Increase the separation between the equipment and
receiver.
° Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
° Consult the dealer or an experienced radio/TV
technician for help.
Copyright ©2007 Linear LLC
227975 A
|